DocuTech 128/155/180 HighLight Color Installation Planning Guide 4-29
Prepare for installation
Table 4-12. Printer (50 Hz) WYE (Star) 380 and 400 voltage.
Printer power outlet/
cord voltage
configurations–
50 Hz
For 50 Hz systems outlet/power cord configurations, consult your
local service representative to determine the type of plug and
receptacle to use.
5 Wire 415 V Line 1 to Line 3 415 V RMS 374-457 V RMS
5 Wire 415 V Line 1 to neutral 240 V RMS 216-264 V RMS
5 Wire 415 V Line 2 to neutral 240 V RMS 216-264 V RMS
5 Wire 415 V Line 3 to neutral 240 V RMS 216-264 V RMS
Service
outlet
configuration
Measurement
of wiring
Nominal Range
5 Wire 380 V Line 1 to line 2 380 V RMS 342-419 V
RMS
5 Wire 380 V Line 2 to line 3 380 V RMS 342-419 V
RMS
5 Wire 380 V Line 1 to Line
3
380 V RMS 342-419 V
RMS
5 Wire 380 V Line 1 to
neutral
220 V RMS 198-242 V
RMS
5 Wire 380 V Line 2 to
neutral
220 V RMS 198-242 V
RMS
5 Wire 380 V Line 3 to
neutral
220 V RMS 198-242 V
RMS
5 Wire 400 V Line 1 to line 2 400 V RMS 358-438 V
RMS
5 Wire 400 V Line 2 to line 3 400 V RMS 358-438 V
RMS
5 Wire 400 V Line 1 to Line
3
400 V RMS 358-438 V
RMS
5 Wire 400 V Line 1 to
neutral
230 V RMS 207-253 V
RMS
5 Wire 400 V Line 2 to
neutral
230 V RMS 207-253 V
RMS
5 Wire 400 V Line 3 to
neutral
230 V RMS 207-253 V
RMS
Service
outlet
configuration
Measurement
of wiring
Nominal Range