4-32 DocuTech 128/155/180 HighLight Color Installation Planning Guide
Prepare for installation
Option 2:
Two-Phase of a three-phase Branch Circuit (2 lines and neutral,
plus ground; total 4-wire system, including ground).
Line to neutral: 120 V (nominal); Range 107 V (minimum) to 127 V
(maximum)
Line to line: 208 V (nominal); Range 185 V (minimum) to 220 V
(maximum)
Cord 2:
30 amp. per line
NEMA 14-30P connector
Single service dedicated lines. 3 wires plus ground.
Option 1:
Single Phase Branch Circuit: (2 lines and neutral, plus ground;
total 4 wires, including ground).
Line to neutral: 120 V (nominal); Range 107 V (minimum) to 127 V
(maximum)
Line to line: 240 V (nominal); Range 210 V (minimum) to 254 V
(maximum)
Option 2:
Two-Phase of a three-phase Branch Circuit (2 lines and neutral,
plus ground; total 4-wire system, including ground).
Line to neutral: 120 V (nominal); Range 107 V (minimum) to 127 V
(maximum)
Line to line: 208 V (nominal); Range 185 V (minimum) to 220 V
(maximum)
50 Hz (one power cord)
Plug configured for site based on local requirements.
Single service dedicated line with 3 phase power.
Voltage Range is line to neutral 198 to 254 VAC measured at the
IOT terminal box.
30 amp per phase
50 Hz (+/- 1.0 Hz)
Delta service is not supported.